CURRENT RATING | C TYPE CODE | D TYPE CODE |
6A | BBD4064CHH | BBD4064DHH |
10A | BBD4104CHH | BBD4104DHH |
16A | BBD4164CHH | BBD4164DHH |
20A | BBD4204CHH | BBD4204DHH |
25A | BBD4254CHH | BBD4254DHH |
32A | BBD4324CHH | BBD4324DHH |
40A | BBD4404CHH | BBD4404DHH |
50A | BBD4504CHH | BBD4504DHH |
63A | BBD4634CHH | BBD4634DHH |
IS/IEC 60898-1:2008
DIN43-883
Type | B | C | D |
Magnetic Release Setting | (3-5)ln | (5-10)ln | (10-20)ln |
No. of Poles (Execution) | SP | SP, SP+N, DP, TP, TP+N, FP | SP, DP, TP, FP |
Rated Current(ln) A | 6A to 63A | ||
Rated Voltage(Ue) | SP, TP+N: AC 240/415V, SP+N: AC 240V, DP, TP, FP: AC 415V | ||
Rated Frequency(f) Hz | 50 Hz | ||
Rated Short Circuit Breaking Capacity | 10000A | ||
Service Short Circuit Breaking Capacity | 7500A | ||
Energy Limitation | Class 3 | ||
Tripping Mechanism | Thermal and Magnetic Type | ||
Normal Ambient Temperature | 30º | ||
Power Loss | Much Less than Standard Values | ||
Rated Impulse Voltage | 4kV | ||
Dielectric Strength | 2000V for 1 minute | ||
Protection Class | IP20 | ||
Mounting | On DIN Rail (35mm X 7.5 mm) | ||
Connections | 1 sq.mm to 25sq.mm For Cu conductors |