RATING | TRIPPING CURRENT | CODE |
25A | 30mA | BBDR42530H |
100mA | BBDR42540H | |
32A | 30mA | BBDR43230H |
100mA | BBDR43240H | |
40A | 30mA | BBDR44030H |
100mA | BBDR44040H | |
300mA | BBDR44050H | |
63A | 30mA | BBDR46330H |
100mA | BBDR46340H | |
300mA | BBDR46350H |
No.of Poles (Execution) | DP, FP |
Rated Current (In) | 25A, 32A, 40A, 63A |
Rated Voltage(Ue) | DP: AC 240V, FP: AC 240/415V |
Rated Frequency(f) | 50Hz |
Sensitivity | 30mA, 100mA, 300mA |
Short Circuit Withstand Capacity | DP:10000A, FP: 6000A |
Short Circuit Breaking Performance Rated conditional Short-circuit (Inc) Rated conditional Residual Short-circuit Current (IΔc) |
DP: 10000A, FP: 6000A |
Rated Making And Breaking Capacity (Im) Rated Residual Making And Breaking Capacity (IΔm) |
DP: 630A FP: 630A |
Mode | Electro-Magnetic Type |
Rated Impulse Voltage | 4kV |
Vibration Resistence | 5G |
Dielectric Strength | 2000V 1min |
Protection Class | IP20 |
Mounting | On DIN Rail 35mm X 7.5mm |
Connections | 1.5sq.mm to 25sq.mm |