• SPN ACCL

    SPN ACCL

 

CODE

DESCRIPTION M.R.P.

CODE

DESCRIPTION
98600   30/0.5A UNO SPN ACCL 2160 98608 30/09A UNO SPN ACCL
98601    30/1.0A UNO SPN ACCL 2160 98612 30/10A UNO SPN ACCL
98602    30/1.5A UNO SPN ACCL 2160 98609 30/12A UNO SPN ACCL
98603  30/2.5A UNO SPN ACCL 2160 98610 30/15A UNO SPN ACCL
98604  30/03A UNO SPN ACCL 2160 98611 30/20A UNO SPN ACCL
98605  30/04A UNO SPN ACCL 2160 98613 30/25A UNO SPN ACCL
98606  30/05A UNO SPN ACCL 2160 98614 30/30A UNO SPN ACCL
98607 30/06A UNO SPN ACCL 2160    

 

AUTOMATIC CHANGE OVER WITH CURRENT LIMITER(ACCL)

A changeover device transfers the Load from Mains Power Supply to the Generator, automatically upon failure of Mains Power Supply. It also functions as a load limiter with monitoring of the Generator supply, thereby reducing stress on the Generator. 

Technical Specification:

FEATURES UNO ACCL
Standard Conformity IEC60947-3 /IEC60947-6
No. of Poles SPN
Mains Current Rating(In) 30A
Gen Current Rating(In) 0.5 to 20A
Rated Voltage(Ue) 240Vac, 50Hz
Rated Impulse Voltage 2.5kV
Design Contactor Based Design
Housing Material Thermoplastic, FR Grade
Class of Equipment PC
Duty Continuous
Utilisation Category  AC22A(IEC 60947-3), AC32A (IEC 60947-6)
Conditional Short -Circuit Current(Inc) 5kA
Electrical Life 25000 Operations
Power Losses 0.2VA Mains, 15VA Gen
Pollution Degree  3
Protection  IP 20
Led Indications Mains, Gen, Overload
Wiring Termination Bottom to Top Wiring
Operating Temperature -50 to +550 C
Terminal Capacity  10mm2
Reset Provision Auto Reset
Tripping Accuracy ±10% of Trip Current
Timing Accuracy ±5%
Mounting Mounting Rail(35x 7.5mm)
Mounting Position vertical / Horizontal 