CODE |
ITEM DESCRIPTION |
CODE |
ITEM DESCRIPTION |
98615 | Uno 40A/6A TPN/SPN ACCL | 98630 | Uno 40A/6A TPN/TPN ACCL |
98616 | Uno 40A/10A TPN/SPN ACCL | 98631 | Uno 40A/10A TPN/TPN ACCL |
98617 | Uno 40A/16A TPN/SPN ACCL | 98632 | Uno 40A/16A TPN/TPN ACCL |
98618 | Uno 40A/20A TPN/SPN ACCL | 98633 | Uno 40A/20A TPN/TPN ACCL |
98619 | Uno 40A/25A TPN/SPN ACCL | 98634 | Uno 40A/25A TPN/TPN ACCL |
98620 | Uno 40A/32A TPN/SPN ACCL | 98635 | Uno 40A/32A TPN/TPN ACCL |
98621 | Uno 40A/40A TPN/SPN ACCL | 98636 | Uno 40A/40A TPN/TPN ACCL |
A changeover device, which on failure of Mains power supply, automatically transfers the Load from Mains power supply to Generator supply. It also functions as a Load Limiter with monitoring of current drawn from Generator, thereby reducing stress on the Generator.
FEATURES | UNO ACCL |
Standard Conformity | IEC 60947-6 |
Versions | TPN/SPN and TPN/TPN |
Mains Current & Voltage | 40A & 415V ~ (P-P) |
Gen Current & Voltage | 6-40A & 230V~(P-N) & 6-40A & 415V ~(P-P) |
Frequency | 50Hz |
Rated impulse voltage(Uimp) | 6kV |
Duty | Continuous duty |
Utilization category | AC32A |
Conditional short circuit | 5kA |
Electrical life | 25000 ops. |
Power consumption | <8VA (Mains/ GEN) |
Protection | IP20 (Terminal Enclosure) |
Pollution degree | III |
Operating temperature | -5 to 55°C |
Mounting | Panel mounting |
Weight | 2.3kg (Unpacked) |
Operating position | Horizontal/ Vertical |
Tripping accuracy | ± 5-10% of Trip current |
Timing accuracy | ±5% |